Modbus TCP/RTU Pulse Counter and Datalogger with 32 Channels
Data acquisition Modules

DIN-32

The DIN-32 Module is a versatile pulse counter and datalogger with 32 discrete input channels, fully compliant with Modbus TCP and Modbus RTU protocols. It provides real-time data acquisition with each record timestamped using an integrated Real-Time Clock (RTC). Designed for industrial applications, the DIN-32 offers robust communication options and seamless integration with both Advanticsys gateways and third-party systems.


32 Discrete Inputs

Handles up to 32 sink/contact digital inputs, supporting contact, impulse, and alarm signals.

Modbus Compatibility

Fully supports Modbus RTU and Modbus TCP protocols, ensuring seamless integration into industrial networks.

Galvanic Isolation

1000V galvanic isolation between power supply and interfaces ensures safe and reliable operation.

DIN Rail Mounting

Compact and durable design with easy DIN rail installation for industrial environments.
  • Key features
  • Technical description

32 Discrete Inputs: Handles up to 32 sink/contact digital inputs, supporting contact, impulse, and alarm signals.

Modbus TCP/RTU Support: Fully compliant with both Modbus TCP and Modbus RTU protocols for easy integration into industrial networks.

Flexible Communication Options: Includes RS232, RS485, Ethernet, and USB interfaces for diverse connection needs.

Galvanic Isolation: Provides electrical isolation between power supply and interfaces (≥1000V), ensuring safe and reliable operation.

Seamless Integration: Easily integrates with Advanticsys gateways or third-party systems, offering flexible deployment options.

General

Power Supply:  9 – 36 VDC

Overvoltage Protection: >1000V (max. 5 seconds)

Power Consumption: 200 mA max

Galvanic Isolation: ≥ 1000V

Processing and Storage

CPU: ARM7

Flash memory: 8MB (up to 5 years storage)

Communication Interfaces

RS232: Up to 15m, speed up to 38400 bps

RS485: Up to 1.2 km, speed up to 38400 bps

USB: Type B, version 2.0

Ethernet: RJ45, 10/100 Mbps, range up to 100m

Discrete Inputs

Channels: Up to 32 sink/contact inputs

Supported Protocols

Modbus RTU, Modbus TCP, IP, ICMP, UDP, TCP, DHCP, PPP, ARP, IEC60870-5-104:2000

Working Conditions

Operating temperature: -25°C to +60°C

Storage temperature: -40°C to +60°C

Humidity range: 5% to 95% (non-condensing)