The AIM-8 Module is a versatile analog input datalogger designed to collect precise measurements from up to 8 channels, supporting Pt100 probes, voltage, and current inputs. It seamlessly integrates with Modbus RTU and Modbus TCP systems, offering compatibility with various industrial setups. With its robust design and compact DIN rail mounting, the AIM-8 ensures reliable operation in demanding environments, making it ideal for industrial data acquisition applications.
8 Analog Input Channels: Supports multiple input types, including Pt100 probes, voltage (0-10V, 0-5V), and current (0/4-20mA).
Modbus RTU/TCP Support: Compatible with both Modbus RTU and Modbus TCP protocols, ensuring seamless integration into industrial networks.
Flexible Interface Options: Equipped with RS485, RS232, and Ethernet interfaces for flexible communication.
High Accuracy: Features ±0.2% accuracy for precise measurement of current, voltage, and resistance signals.
Data Logging Capabilities: Internal flash memory for archiving data, with up to 8 MB of storage and battery backup for up to 5 years.
Durable and Reliable: Operating temperature range from -25°C to +60°C, with IP20 protection.
Galvanic Isolation: Ensures safe and reliable operation with 1000V isolation between power supply and communication interfaces.
DIN Rail Mounting: Compact design with DIN rail compatibility for easy installation in industrial environments.
Easy Integration: Can be used as a Modbus slave extension module with Advanticsys gateways or third-party Modbus masters.
General
Power Supply: 9 – 36 VDC
Overvoltage Protection: >1000V (max. 5 seconds)
Power Consumption: <10 VA
Galvanic Isolation: ≥ 1000V
Processing and Storage
CPU: ARM7
Flash memory: 8MB (up to 5 years storage)
Communication Interfaces
RS232: Up to 15m, speed up to 57600 bps
RS485: Up to 1.2 km, speed up to 57600 bps
USB: Type B, version 2.0
Ethernet: RJ45, 10/100 Mbps, range up to 100m
Analog Inputs
Current: 0/4-20mA,0-5 mA ±0,2%,input resistance 250Ω
Voltage: 0-10V, 0-5V ±0,2%, input resistance 10kΩ
PT100: 80-250Ω (-50 to +400ºC) ±0,2%
PT1000: 850-1950Ω (-40 to +250ºC) ±0,2%
Resistance: 0-30kΩ ±0,2%
Supported Protocols
Modbus RTU, Modbus TCP/IP, IP, ICMP, UDP, TCP, DHCP, PPP, ARP, IEC60870-5-104:2000
Working Conditions
Operating temperature: -25°C to +60°C
Storage temperature: -40°C to +60°C
Humidity range: 5% to 95% (non-condensing)