MPC-333

From Advanticsys Tech Resources
Jump to: navigation, search

The MPC-333 is a datalogger / controller developed to communicate with the most common protocols such as M-Bus, Modbus TCP Ethernet, Modbus TCP/IP, Modbus RTU, DATA/Req, IEC60870-5-104: 2000, and a special transparent mode for special manufacturer protocols, so almost any device can be connected.

MPC-333 Modbus Ethernet Gateway can also measure and store different kinds of discrete signals like those from limit switches, push buttons, alarms, relay contacts...

Using open standard protocol (Modbus), it can also send stored data to remote user through GSM/GPRS modem or Modbus Ethernet port (LAN/Internet), greatly simplifying the systems integration into SCADA / user software.


Features

Item Specification
Overall specifications
CPU ARM7
Flash archive storage of 2 MB, battery backup, data valid up to 5 years
GSM/GPRS 3 band 900/1800/1900 MHz
Interfaces
RS232 (1 port) up to 15m (50ft), speed up to 19,2 Kbits/s
RS485 (1 port) up to 1.2 km (0.75 mi), max 32 transceivers, up to 19.2 Kbits/s
M-Bus (1 port) up to 8 devices
USB (1 port) type B, ver. 2.0
Ethernet (1 port) twisted pair Ethernet 10/100 Mb, up to 100m (328ft)
Discrete Inputs
Channels 8
Input type Sink type
Protocols
Modbus RTU, Modbus TCP/IP, IP, ICMP, UDP, TCP, DHCP, PPP, ARP, SNTP, IEC60870-5-104:2000 (IEC 104)
General
Power supply 9-36 VDC / 10VA
Over voltage protection >1000V
Power consumption <10VA
Physical Characteristics
Dimensions 197x128x50 mm
Weight 400 g
Case fixing type DIN rail
Safety class IP20

Resources

References